Ideal Product Categories

About Us

cable, vdsl, patch

 

Hyperline- Ideal Industries Cutters - Coax/Twisted Pair Cutters - Twisted Pair Cutters - Coax Cutters - Fiber Cutters Fiber Optic Test Equipment- Ideal Industries


American Tech Supply is now an authorized Hyperline distributor

From copper to fiber, the Hyperline system of products includes everything you need for installation, termination, testing and troubleshooting. And our level of technical expertise, training and customer support ensures that your total cost of ownership is kept to a minimum.

Calcium Sulphate Access Floor

Design
The high-density NORTEC calcium sulphate panels are manufactured with selected raw materials in a patented single-pulse pressing procedure. This combination guarantees a consistently high-quality product. As reinforcing material, only nontoxic, unbleached cellulose fibers of primary and secondary cellulose are used. This enables us to manufacture a product of consistently superior quality. The panel can be supplied with or without an edge band (dependent on the floor covering applied); these being tapered for easier installation of the integrated panel system. The underside may be additionally lined with galvanized steel sheet or aluminum foil.
Calcium sulphate panel
The support elements used have been specially developed for use with access flooring. The main components of these panels are gypsum and high-quality cellulose fibers. Various thicknesses of the panels, as well as special formats, round off the NORTEC line of products. To be able to manufacture standard access floor panels with extra static requirements, and without increasing the thickness of the panels, a special manufacturing process was developed to meet growing demands.
Design of the edges
The edges of the panels are tapered down at 5?, which enables simple removal and exchange of the integrated panel system. As an option, the panels can be jacketed with a high-quality plastic compound edge, which offers a defined electrostatic conductivity.
Coating of the lower face of the panel
The increased strength of ST-type panels is based on 0.5 mm (0.02”) thick galvanized steel sheet on the lower face of the panel.
Floor coverings
Generally, all common access floor coverings are suited. In the standard design, the edge is, with elastic coverings, pulled up to the upper surface of the covering (exception: knobby floor coverings). When applying loosely laid floor coverings, we recommend providing the carrier panels with an appropriate coating.
Special features
Individual panel thickness
The panel edges are beveled downward, simplify mounting and replacement of the panels
Meet the strictest requirements of fire safety F60
To increase the eventual load capacity, the lower surface of the panel may be coated with an iron plate
The panel edges are covered with plastic, which provides optimal board contact
Stringers and other optional components of the system make it possible to increase the strength of the construction
Range of use
Computer rooms and control rooms
Industrial and factory rooms
Training and research rooms
Office and designing areas

Construction
  1. Optional surface coating
  2. Protective edging of the panel depending on the coating type
  3. Calcium sulfate panel
  4. For panels with lower coating (ST-type) ? iron plate coating
  1. Panel (fiber-strengthened gypsum)
  2. Gusset for the support top
  3. Lateral edge (optional)
  4. Access floor support
  5. Support base
  6. Main floor
Fire resistance
The steadily increasing demand for using incombustible materials to reduce risk of fire in buildings makes the Hyperline Calcium Sulphate Access Floor a very valuable solution, which offers both functional and safety advantages. Superior fire resistance and alevel of comfort are the main features of the Hyperline Calcium Sulphate Access Floor ? a most intelligent solution.

High degree of flexibility
Standard panel thicknesses between 0.9” to 1.6” (24 to 40 mm), as well as unique material combinations are available to accommodate any specific load-bearing requirement ? tailor-made solutions can be offered as standard.

Acoustic characteristics
The material structure, design features, and high precision production of the access floor panels provide excellent acoustic values. The great walking properties offer a high degree of comfort and create the perfect working environment.

Electrostatic characteristics
Electrostatic charges are dissipated, regardless of panel material, by the inherent design features. The ohmic resistance defined in this way allows grounding compliance in accordance with VDE 0100 using suitable floor coverings.

Air ventilation
Either plastic or metal ventilation components can be fitted into the calcium sulphate panel, or steel ventilation panels can be installed instead of NORTEC panels, in order to accommodate the requirements of the sub-floor air conditioning system.

Ecology
Due to the environmentally-friendly production process, and the use of ecologically safe materials, 90 to 97% of the Hyperline panels will be recyclable at the end of their life ? a very important ecological consideration today.

System specifications
System designation NORTEC
Type MS13-ST-ST MS15-ST-ST MH18-ST MS20-ST
Description
Panel/material Calcium sulphate panel with bevelled edges, steel sheet on bottom and top sides Calcium sulphate panel, optionally with edge trim, steel sheet on bottom side
Dimensions 600 x 600 mm (23.6” x 23.6”)
Panel thickness 14 mm (0.55”) 16 mm (0.6”) 18.5 mm (0.7”) 20.5 mm (0.8”)
System weight1 29 kg/m2?
(5.9 lbs/ft2)
32 kg/m2?
(6.6 lbs/ft2)
33 kg/m2(6.8 lbs/ft2) 36 kg/m2?(7.4 lbs/ft2)
Substructure with construction heights?> 500 mm (19.7”) Steel pedestals RO stringer
Construction height2 From 22 mm (0.86”), special flooring system for areas undergoing renovations with extremely low finished floor heights
Load capacity rating (Nominal load) See "STATICS" supplement
Fireproofing3?Building Material Class of the panel A1 (non-combustible)
Soundproofing4 Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering(VM = 26 dB)
Rated degree of longitudinal sound reduction 42 dB - - 50 dB - 50 dB
Sound insulation index - - - - - -
Rated footfall sound level - 22 dB - 53 dB - 53 dB
Degree of improvement in footfall sound - - - 22 dB - 22 dB
Suitability of coverings Loosely laid tiles
Electric conductivity5 >= 106?O

1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed
5) The values are affected by the floor covering

System specifications
System designation NORTEC
Type MU24-ST MS30 MU30-ST MU30-ST-ST
Description
Panel/material Calcium sulphate panel with bevelled edges, steel sheet on bottom Calcium sulphate panel with bevelled edges Calcium sulphate panel, optionally with edge trim with steel sheet on bottom side Calcium sulphate panel, optionally with edge trim with steel sheet on bottom and top side
Dimensions 600 x 600 mm (23.6” x 23.6”)
Panel thickness 24.5 mm (1”) 30 mm (1.18”) 30.5 mm (1.2”) 31 mm (1.22”)
System weight1 42 kg/m2?
(8.6 lbs/ft2)
47 kg/m2?
(9.6 lbs/ft2)
52 kg/m2?
(10.7 lbs/ft2)
55 kg/m2?
(11.3 lbs/ft2)
Substructure with construction heights> 500 mm (19.7”) Steel pedestals RO stringer
Construction height2 28 ? 2 000 mm (1.1” ? 7 8.7”) 28 ? 1 450 mm?(1.1” ? 57.1”)
Load capacity rating (Nominal load) See "STATICS" supplement
Fireproofing3?Building Material Class of the panel A1 (non-combustible)
Soundproofing4 Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering?(VM = 26 dB)
Rated degree of longitudinal sound reduction 49 dB 50 dB 48 dB 48 dB 48 dB 48 dB
Sound insulation index 62 dB - 62 dB - 62 dB -
Rated footfall sound level 65 dB 47 dB 73 dB 47 dB 73 dB 47 dB
Degree of improvement in footfall sound - - - - - -
Suitability of coverings Textile coverings, Elastic coverings, Loosely laid tiles, WOODline Textile coverings, Elastic coverings, Loosely laid tiles, WOODline, STONEline Loosely laid tiles
Electric conductivity5 >= 106?O

1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed
5) The values are affected by the floor covering

System specifications
System designation NORTEC
Type MS36 MU36-ST MX40 MS38-ST
Description
Panel/material Calcium sulphate panel, optionally with edge trim Calcium sulphate panel, optionally with edge trim with steel sheet on bottom Calcium sulphate panel, optionally with edge trim Calcium sulphate panel, optionally with edge trim with steel sheet on bottom
Dimensions 600 x 600 mm (23.6” x 23.6”)
Panel thickness 36 mm (1.4”) 36.5 mm (1.44”) 40 mm (1.6”) 38.5 mm (1.5”)
System weight1 56 kg/m2?
(11.5 lbs/ft2)
61 kg/m2?
(12.5 lbs/ft2)
62 kg/m2(12.7 lbs/ft2) 61 kg/m2?
(12.5 lbs/ft2)
Substructure with construction heights> 500 mm (19.7”) Steel pedestals RO stringer
Construction height2 28 ? 2 000 mm(1.1” ? 7 8.7”) 28 ? 1 450 mm (1.1” ? 57.1”)
Load capacity rating (Nominal load) See "STATICS" supplement
Fireproofing3?Building Material Class of the panel A1 (non-combustible) F60/REI 60
Soundproofing4 Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering?(VM = 26 dB)
Rated degree of longitudinal sound reduction 50 dB 51 dB 49 dB - 49 dB -
Sound insulation index 62 dB - 62 dB - 62 dB -
Rated footfall sound level 70 dB 52 dB 70 dB - 70 dB -
Degree of improvement in footfall sound 14 dB 28 dB 14 dB - 14 dB -
Suitability of coverings Textile coverings, Elastic coverings, Loosely laid tiles, WOODline, STONEline
Electric conductivity5 >= 106?O

1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed; values of the 36 mm (1.4”) panel tested
5) The values are affected by the floor covering

System specifications
System designation NORTEC
Type MS36-H12-CM MU36-ST-RM MS36-CL MH36-CL
Description
Panel/material Calcium sulphate panel, optionally with edge trim Calcium sulphate panel, optionally with edge trim with steel sheet on bottom side Calcium sulphate panel, optionally with edge trim
Dimensions 600 x 600 mm (23.6” x 23.6”)
Panel thickness 36 mm (1.4”) 36.5 mm (1.44”) 36 mm (1.4”)
System weight1 63 kg/m2?(12.9 lbs/ft2) 65 kg/m2(13.3 lbs/ft2)
Substructure with construction heights?> 500 mm (19.7”) Steel pedestals Grid: 600x1200 mm (23.6”x47.2”) CM-profile Steel pedestals RM stringer Steel pedestals CL-profile
Construction height2 28 ? 1450 mm (1.1” ? 57.1”)
Load capacity rating (Nominal load) See "STATICS" supplement
Fireproofing3?Building Material Class of the panel A1 (non-combustible) A1 (non-combustible) supplement F30 / REI 30
Soundproofing4 Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering(VM = 26 dB) Without floor covering With floor covering(VM = 26 dB)
Rated degree of longitudinal sound reduction 50 dB 51 dB 49 dB - 50 dB 51 dB
Sound insulation index 62 dB - 62 dB - 62 dB -
Rated footfall sound level 70 dB 52 dB 70 dB - 70 dB 52 dB
Degree of improvement in footfall sound 14 dB 28 dB 14 dB - 14 dB 28 dB
Suitability of coverings Textile coverings, Elastic coverings, Loosely laid tiles, WOODline, STONEline
Electric conductivity5 >= 106?O

1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed