American Tech Supply is now an authorized Hyperline distributor
From copper to fiber, the Hyperline system of products includes everything you need for installation, termination, testing and troubleshooting. And our level of technical expertise, training and customer support ensures that your total cost of ownership is kept to a minimum.
Calcium Sulphate Access Floor
Design
The high-density NORTEC calcium sulphate panels are manufactured with selected raw materials in a patented single-pulse pressing procedure. This combination guarantees a consistently high-quality product. As reinforcing material, only nontoxic, unbleached cellulose fibers of primary and secondary cellulose are used. This enables us to manufacture a product of consistently superior quality. The panel can be supplied with or without an edge band (dependent on the floor covering applied); these being tapered for easier installation of the integrated panel system. The underside may be additionally lined with galvanized steel sheet or aluminum foil.
Calcium sulphate panel
The support elements used have been specially developed for use with access flooring. The main components of these panels are gypsum and high-quality cellulose fibers. Various thicknesses of the panels, as well as special formats, round off the NORTEC line of products. To be able to manufacture standard access floor panels with extra static requirements, and without increasing the thickness of the panels, a special manufacturing process was developed to meet growing demands.
Design of the edges
The edges of the panels are tapered down at 5?, which enables simple removal and exchange of the integrated panel system. As an option, the panels can be jacketed with a high-quality plastic compound edge, which offers a defined electrostatic conductivity.
Coating of the lower face of the panel
The increased strength of ST-type panels is based on 0.5 mm (0.02”) thick galvanized steel sheet on the lower face of the panel.
Floor coverings
Generally, all common access floor coverings are suited. In the standard design, the edge is, with elastic coverings, pulled up to the upper surface of the covering (exception: knobby floor coverings). When applying loosely laid floor coverings, we recommend providing the carrier panels with an appropriate coating.
Special features
Individual panel thickness
The panel edges are beveled downward, simplify mounting and replacement of the panels
Meet the strictest requirements of fire safety F60
To increase the eventual load capacity, the lower surface of the panel may be coated with an iron plate
The panel edges are covered with plastic, which provides optimal board contact
Stringers and other optional components of the system make it possible to increase the strength of the construction
Range of use
Computer rooms and control rooms
Industrial and factory rooms
Training and research rooms
Office and designing areas
Construction
Optional surface coating
Protective edging of the panel depending on the coating type
Calcium sulfate panel
For panels with lower coating (ST-type) ? iron plate coating
Panel (fiber-strengthened gypsum)
Gusset for the support top
Lateral edge (optional)
Access floor support
Support base
Main floor
Fire resistance
The steadily increasing demand for using incombustible materials to reduce risk of fire in buildings makes the Hyperline Calcium Sulphate Access Floor a very valuable solution, which offers both functional and safety advantages. Superior fire resistance and alevel of comfort are the main features of the Hyperline Calcium Sulphate Access Floor ? a most intelligent solution.
High degree of flexibility
Standard panel thicknesses between 0.9” to 1.6” (24 to 40 mm), as well as unique material combinations are available to accommodate any specific load-bearing requirement ? tailor-made solutions can be offered as standard.
Acoustic characteristics
The material structure, design features, and high precision production of the access floor panels provide excellent acoustic values. The great walking properties offer a high degree of comfort and create the perfect working environment.
Electrostatic characteristics
Electrostatic charges are dissipated, regardless of panel material, by the inherent design features. The ohmic resistance defined in this way allows grounding compliance in accordance with VDE 0100 using suitable floor coverings.
Air ventilation
Either plastic or metal ventilation components can be fitted into the calcium sulphate panel, or steel ventilation panels can be installed instead of NORTEC panels, in order to accommodate the requirements of the sub-floor air conditioning system.
Ecology
Due to the environmentally-friendly production process, and the use of ecologically safe materials, 90 to 97% of the Hyperline panels will be recyclable at the end of their life ? a very important ecological consideration today.
System specifications
System designation
NORTEC
Type
MS13-ST-ST
MS15-ST-ST
MH18-ST
MS20-ST
Description
Panel/material
Calcium sulphate panel with bevelled edges, steel sheet on bottom and top sides
Calcium sulphate panel, optionally with edge trim, steel sheet on bottom side
Dimensions
600 x 600 mm (23.6” x 23.6”)
Panel thickness
14 mm (0.55”)
16 mm (0.6”)
18.5 mm (0.7”)
20.5 mm (0.8”)
System weight1
29 kg/m2?
(5.9 lbs/ft2)
32 kg/m2?
(6.6 lbs/ft2)
33 kg/m2(6.8 lbs/ft2)
36 kg/m2?(7.4 lbs/ft2)
Substructure with construction heights?> 500 mm (19.7”)
Steel pedestals RO stringer
Construction height2
From 22 mm (0.86”), special flooring system for areas undergoing renovations with extremely low finished floor heights
Load capacity rating (Nominal load)
See "STATICS" supplement
Fireproofing3?Building Material Class of the panel
A1 (non-combustible)
Soundproofing4
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering(VM = 26 dB)
Rated degree of longitudinal sound reduction
42 dB
-
-
50 dB
-
50 dB
Sound insulation index
-
-
-
-
-
-
Rated footfall sound level
-
22 dB
-
53 dB
-
53 dB
Degree of improvement in footfall sound
-
-
-
22 dB
-
22 dB
Suitability of coverings
Loosely laid tiles
Electric conductivity5
>= 106?O
1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed
5) The values are affected by the floor covering
System specifications
System designation
NORTEC
Type
MU24-ST
MS30
MU30-ST
MU30-ST-ST
Description
Panel/material
Calcium sulphate panel with bevelled edges, steel sheet on bottom
Calcium sulphate panel with bevelled edges
Calcium sulphate panel, optionally with edge trim with steel sheet on bottom side
Calcium sulphate panel, optionally with edge trim with steel sheet on bottom and top side
Dimensions
600 x 600 mm (23.6” x 23.6”)
Panel thickness
24.5 mm (1”)
30 mm (1.18”)
30.5 mm (1.2”)
31 mm (1.22”)
System weight1
42 kg/m2?
(8.6 lbs/ft2)
47 kg/m2?
(9.6 lbs/ft2)
52 kg/m2?
(10.7 lbs/ft2)
55 kg/m2?
(11.3 lbs/ft2)
Substructure with construction heights> 500 mm (19.7”)
Steel pedestals RO stringer
Construction height2
28 ? 2 000 mm (1.1” ? 7 8.7”)
28 ? 1 450 mm?(1.1” ? 57.1”)
Load capacity rating (Nominal load)
See "STATICS" supplement
Fireproofing3?Building Material Class of the panel
A1 (non-combustible)
Soundproofing4
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering?(VM = 26 dB)
Rated degree of longitudinal sound reduction
49 dB
50 dB
48 dB
48 dB
48 dB
48 dB
Sound insulation index
62 dB
-
62 dB
-
62 dB
-
Rated footfall sound level
65 dB
47 dB
73 dB
47 dB
73 dB
47 dB
Degree of improvement in footfall sound
-
-
-
-
-
-
Suitability of coverings
Textile coverings, Elastic coverings, Loosely laid tiles, WOODline
Textile coverings, Elastic coverings, Loosely laid tiles, WOODline, STONEline
Loosely laid tiles
Electric conductivity5
>= 106?O
1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed
5) The values are affected by the floor covering
System specifications
System designation
NORTEC
Type
MS36
MU36-ST
MX40
MS38-ST
Description
Panel/material
Calcium sulphate panel, optionally with edge trim
Calcium sulphate panel, optionally with edge trim with steel sheet on bottom
Calcium sulphate panel, optionally with edge trim
Calcium sulphate panel, optionally with edge trim with steel sheet on bottom
Dimensions
600 x 600 mm (23.6” x 23.6”)
Panel thickness
36 mm (1.4”)
36.5 mm (1.44”)
40 mm (1.6”)
38.5 mm (1.5”)
System weight1
56 kg/m2?
(11.5 lbs/ft2)
61 kg/m2?
(12.5 lbs/ft2)
62 kg/m2(12.7 lbs/ft2)
61 kg/m2?
(12.5 lbs/ft2)
Substructure with construction heights> 500 mm (19.7”)
Steel pedestals RO stringer
Construction height2
28 ? 2 000 mm(1.1” ? 7 8.7”)
28 ? 1 450 mm (1.1” ? 57.1”)
Load capacity rating (Nominal load)
See "STATICS" supplement
Fireproofing3?Building Material Class of the panel
A1 (non-combustible) F60/REI 60
Soundproofing4
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering?(VM = 26 dB)
Rated degree of longitudinal sound reduction
50 dB
51 dB
49 dB
-
49 dB
-
Sound insulation index
62 dB
-
62 dB
-
62 dB
-
Rated footfall sound level
70 dB
52 dB
70 dB
-
70 dB
-
Degree of improvement in footfall sound
14 dB
28 dB
14 dB
-
14 dB
-
Suitability of coverings
Textile coverings, Elastic coverings, Loosely laid tiles, WOODline, STONEline
Electric conductivity5
>= 106?O
1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed; values of the 36 mm (1.4”) panel tested
5) The values are affected by the floor covering
System specifications
System designation
NORTEC
Type
MS36-H12-CM
MU36-ST-RM
MS36-CL
MH36-CL
Description
Panel/material
Calcium sulphate panel, optionally with edge trim
Calcium sulphate panel, optionally with edge trim with steel sheet on bottom side
Calcium sulphate panel, optionally with edge trim
Dimensions
600 x 600 mm (23.6” x 23.6”)
Panel thickness
36 mm (1.4”)
36.5 mm (1.44”)
36 mm (1.4”)
System weight1
63 kg/m2?(12.9 lbs/ft2)
65 kg/m2(13.3 lbs/ft2)
Substructure with construction heights?> 500 mm (19.7”)
Steel pedestals Grid: 600x1200 mm (23.6”x47.2”) CM-profile
Steel pedestals RM stringer
Steel pedestals CL-profile
Construction height2
28 ? 1450 mm (1.1” ? 57.1”)
Load capacity rating (Nominal load)
See "STATICS" supplement
Fireproofing3?Building Material Class of the panel
A1 (non-combustible)
A1 (non-combustible) supplement F30 / REI 30
Soundproofing4
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering(VM = 26 dB)
Without floor covering
With floor covering(VM = 26 dB)
Rated degree of longitudinal sound reduction
50 dB
51 dB
49 dB
-
50 dB
51 dB
Sound insulation index
62 dB
-
62 dB
-
62 dB
-
Rated footfall sound level
70 dB
52 dB
70 dB
-
70 dB
52 dB
Degree of improvement in footfall sound
14 dB
28 dB
14 dB
-
14 dB
28 dB
Suitability of coverings
Textile coverings, Elastic coverings, Loosely laid tiles, WOODline, STONEline
Electric conductivity5
>= 106?O
1) Floor height 150 mm (5.9”) (FFH), without covering
2) Clear height, special heights available on request
3) According to DIN 4102/EN 13 501
4) VDI 3762 must be followed
5) The values are affected by the floor covering
Call (866) 342-3721 Or Click On The Chat Button At The Top Of The Page To Talk To One Of Our Representatives