83754 – Electronic, 4 C #14 Str TC, FEP Ins, OS+TC Brd, Red FEP Jkt, CMP FPLP


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: fire alarms; extreme high/low temperature environments; indoor/outdoor applications; low voltage analog signals (4-20ma, 0-10v, …); low voltage control (24v, …)

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 14 AWG 7×22 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) FEP – Fluorinated Ethylene Propylene 0.016 in (0.41 mm) 0.105 in (2.67 mm) Black, White, Red, Green
Outer Shield
Shield Type Material Coverage
Tape Bi-Laminate (Alum+Poly) 100%
Braid Tinned Copper (TC) 85%
Outer Jacket
Material Nom. Thickness Nom. Diameter
FEP – Fluorinated Ethylene Propylene 0.020 in (0.51 mm) 0.321 in (8.15 mm)
Overall Cable Diameter (Nominal): 0.321 in (8.15 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Max. Current
Conductor(s) 2.78 Ohm/1000ft 30 pF/ft (98 pF/m) 52 pF/ft (170 pF/m) 14.4 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
200°C -70°C to +200°C
Bend Radius
Stationary Min. Installation Min.
3.2 in (81 mm) 3.2 in (81 mm)
Max. Pull Tension: 270 lbs (120 kg)
Bulk Cable Weight: 98 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Oil Resistance, Burial
Flammability / Reaction to Fire: NFPA 262 (UL 910), FT6
CPR Compliance: CPR Euroclass: Eca
NEC / UL Compliance: Article 760, Article 800
CEC / C(UL) Compliance: CMP
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation Compliance: UKCA Mark
APAC Compliance: China RoHS II (GB/T 26572-2011)

Product Notes

Notes: Gas Resistant

History

Update and Revision: Revision Number: 0.513 Revision Date: 11-27-2023

Part Numbers

Variants
Item # Color Putup Type Length UPC Footnote
83754 002500 Red Reel 500 ft 612825205715 C
83754 0021000 Red Reel 1,000 ft 612825205708 C