Product Overview
Suitable Applications: | extreme high/low temperature environments; chemical resistant; outdoor and burial applications; low voltage analog signals (4-20ma, 0-10v, …); low voltage control (24v, ); line level audio; voice communications; panel wiring |
Construction Details
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 4 | 18 AWG | 19×30 | TC – Tinned Copper |
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | FEP – Fluorinated Ethylene Propylene | 0.007 in (0.18 mm) | 0.057 in (1.4 mm) | Black, White, Red, Green |
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (19×32) TC |
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
FEP – Fluorinated Ethylene Propylene | 0.014 in (0.36 mm) | 0.173 in (4.39 mm) |
Overall Cable Diameter (Nominal): | 0.173 in (4.39 mm) |
Electrical Characteristics
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Velocity of Prop. | Max. Current |
---|---|---|---|---|---|
Conductor(s) | 7.06 Ohm/1000ft | 30 pF/ft (98 pF/m) | 57 pF/ft (190 pF/m) | 69% | 13.6 Amps per Conductor at 30ºC |
UL Voltage Rating |
---|
300 V (CMP) |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
150°C | -20°C to +150°C |
Stationary Min. | Installation Min. |
---|---|
1.7 in (43 mm) | 1.7 in (43 mm) |
Max. Pull Tension: | 114 lbs (51.7 kg) |
Bulk Cable Weight: | 36 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
Sustainability: | CA Prop 65 |
Flammability / Reaction to Fire: | NFPA 262, UL 910 (Plenum), IEC 60332-1-2 |
CPR Compliance: | CPR Euroclass: Eca |
NEC / UL Compliance: | Article 800, CMP |
CEC / C(UL) Compliance: | CMP |
European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
UK Regulation Compliance: | UKCA Mark |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
Non-Plenum Number: | 9418 |
Product Notes
Notes: | Chemical Resistance: Gasoline |
History
Update and Revision: | Revision Number: 0.527 Revision Date: 11-27-2023 |
Part Numbers
Item # | Color | Putup Type | Length | UPC | Footnote |
---|---|---|---|---|---|
89418 002100 | Red | Reel | 100 ft | 612825220930 | C |
89418 002500 | Red | Reel | 500 ft | 612825220954 | C |
89418 0021000 | Red | Reel | 1,000 ft | 612825220947 | C |
89418 0025000 | Red | Reel | 5,000 ft | 612825220961 | C Z |