Construction Details
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 2 | 14 AWG | 19×26 | BC – Bare Copper |
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PP – Polypropylene | 0.011 in (0.28 mm) | 0.092 in (2.3 mm) | Black, White |
Shield Type | Material | Coverage |
---|---|---|
Tape | Polyester | 100% |
Material | Nom. Thickness | Nom. Diameter | Color |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.017 in (0.43 mm) | 0.230 in (5.84 mm) | Brown |
Armor Type & Material | Armor Thickness | Diameter Over Armor |
---|---|---|
AIA – Aluminum Interlock Armor | 0.025 in (0.64 mm) | 0.45 in (11 mm) |
Overall Cable Diameter (Nominal): | 0.45 in |
Electrical Characteristics
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|---|---|
2.53 Ohm/1000ft | 22 pF/ft (72 pF/m) | 8 Amps per Conductor at 25ºC |
UL Voltage Rating |
---|
300 V |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
75°C | 0°C To +75°C |
Stationary Min. | Installation Min. |
---|---|
4.5 in (110 mm) | 4.5 in |
Max. Pull Tension: | 200 lbs (91 kg) |
Bulk Cable Weight: | 81 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor – Riser, Indoor |
Flammability / Reaction to Fire: | UL1666 Riser |
NEC / UL Compliance: | Article 725, Article 760 |
European Directive Compliance: | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
Plenum Number: | 6100UE |
History
Update and Revision: | Revision Number: 0.242 Revision Date: 12-20-2022 |
Part Numbers
Item # | Color | Putup Type | Length | UPC | Footnote |
---|---|---|---|---|---|
25100UE 0001000 | None | Reel | 1,000 ft | 612825132059 | C |