Product Overview
Suitable Applications: | Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, ),RTD, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, actuators, positioners |
Construction Details
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Triad(s) | 36 | 20 AWG | 7×28 | BC – Bare Copper |
Comm Wire(s) | 1 | 22 AWG | 7×30 | BC – Bare Copper |
Element | Material | Nom. Thickness | Color Code |
---|---|---|---|
Triad(s) | PVC – Polyvinyl Chloride | 0.018 in (0.46 mm) | Black, White, Red and Numbered |
Comm Wire(s) | PVC – Polyvinyl Chloride | 0.019 in (0.48 mm) | Orange |
Element | Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|---|
Triad(s) | Tape | Bi-Laminate (Alum+Poly) | 100% | 22 AWG (7×30) TC |
Comm Wire(s) | No Shield |
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (7×28) TC |
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.074 in (1.9 mm) | 1.156 in (29.36 mm) | Yes |
Overall Cable Diameter (Nominal): | 1.156 in (29.36 mm) |
Electrical Characteristics
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Shield | Max. Current |
---|---|---|---|---|
Triad(s) | 9.5 Ohm/1000ft (31 Ohm/km) | 30 pF/ft (98 pF/m) | 55 pF/ft (180 pF/m) | 3 Amps per conductor @ 25°C |
Comm Wire(s) | 14.7 Ohm/1000ft (48.2 Ohm/km) |
UL Voltage Rating |
---|
300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC) |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
105°C | -30°C to +105°C |
Stationary Min. | Installation Min. |
---|---|
11.6 in (295 mm) | 11.6 in (295 mm) |
Max. Pull Tension: | 1875 lbs (850.5 kg) |
Bulk Cable Weight: | 910 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial |
Flammability / Reaction to Fire: | UL1685 (FT4 Loading), FT4, T-29-520, 1202 |
NEC / UL Compliance: | Article 725, Article 727, Article 800, CMG, ITC, PLTC |
AWM Compliance: | AWM 2464 |
CEC / C(UL) Compliance: | CMG |
European Directive Compliance: | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
Update and Revision: | Revision Number: 0.201 Revision Date: 01-11-2024 |