Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 3 | 12 AWG | 7×20 | BC – Bare Copper |
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.019 in (0.48 mm) | 0.131 in (3.33 mm) | ICEA Chart E1 |
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 14 AWG (7×22) TC |
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.384 in | Yes |
Overall Cable Diameter (Nominal): | 0.384 in |
Electrical Characteristics
Nom. Conductor DCR | Max. Current |
---|---|
1.68 Ohm/1000ft | 24 Amps per Conductor at 30ºC |
UL Voltage Rating |
---|
600 V (TC), 150 V (NPLF) |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
90°C Dry, 75°C Wet | Wet/Dry: -30°C To 90°C |
Stationary Min. | Installation Min. |
---|---|
4.608 in (117.0 mm) | 4.608 in |
Max. Pull Tension: | 315 lbs (143 kg) |
Bulk Cable Weight: | 118 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL Loading, T-29-520, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 336, NPLF, TC-ER, THHN, THWN |
European Directive Compliance: | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
Product Notes
Notes: | Alternate color coding available upon request. |
History
Update and Revision: | Revision Number: 0.283 Revision Date: 06-07-2023 |
Part Numbers
Item # | Putup Type | UPC |
---|---|---|
3104A 0102500 | Reel | 612825334538 |
3104A 0105000 | Reel | 612825334545 |
3104A 0105000 | Reel | 612825334545 |