Product Overview
Suitable Applications: | Survivability, Survivability from Attach by Fire, Fire Alarm Circuit Integrity, CI, Survivability by NFPA72, Sim to MI, Similar to Mineral Insulated, FPLR-CI, Emergency Circuits, Notification Devises, Fire Pumps, 2 hour fire rating |
Physical Characteristics (Overall)
AWG | Stranding | Material | No. of Conductors |
---|---|---|---|
18 | 7×26 | BC – Bare Copper | 4 |
Conductor Count: | 4 |
Material | Nominal Wall Thickness |
---|---|
Silicone Rubber | 0.034 in |
Number | Color |
---|---|
1 | Black#1 |
2 | Black#2 |
3 | Black#3 |
4 | Black#4 |
Type | Material | Material Trade Name | Coverage [%] | Drainwire Material | Drainwire AWG | Drainwire Construction n x D |
---|---|---|---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | Beldfoil® | 100% | TC – Tinned Copper | 20 | 7×28 |
Material | Nominal Diameter | Nominal Wall Thickness |
---|---|---|
PE – Polyethylene | 0.372 in | 0.045 in |
Table Notes: | Flame Retardant |
Electrical Characteristics
Nominal Conductor DCR | Nominal Outer Shield DCR |
---|---|
5.86 Ohm/1000ft | 9 Ohm/1000ft |
Nom. Capacitance Conductor to Conductor |
---|
27 pF/ft |
UL Description | UL Voltage Rating |
---|---|
FPLR only applications | 300 V RMS |
CI applications | 41 V RMS |
Temperature Range
UL Temp Rating: | 105°C |
Operating Temperature Range: | -20°C To +105°C |
Mechanical Characteristics
Bulk Cable Weight: | 94 lbs/1000ft |
Max. Pull Tension: | 89.6 lbs |
Min. Bend Radius/Minor Axis: | 3.75 in |
Standards
NEC/(UL) Compliance: | FPLR-CI |
Applicable Environmental and Other Programs
EU Directive Compliance: | EU Directive 2003/11/EC (BFR) |
EU CE Mark: | Yes |
MII Order #39 (China RoHS): | Yes |
Flammability, LS0H, Toxicity Testing
UL Flammability: | UL1666 Riser,UL2196 Two Hour Circuit Integrity |
UL voltage rating: | 300 V RMS |
Plenum/Non-Plenum
Plenum (Y/N): | No |
History
Update and Revision: | Revision Number: 0.322 Revision Date: 11-30-2023 |