Product Overview
Suitable Applications: | Fire Alarm, SLC Loops, Digital Audio Loops, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
Construction Details
Element | No. of Pairs | Size | Stranding | Material |
---|---|---|---|---|
Pair(s) | 1 | 18 AWG | Solid | BC – Bare Copper |
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|
PP – Polypropylene | .015 in (0.38 mm) | .071 in (1.8 mm) | Black, Red |
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | .030 in (0.76 mm) | .202 | Yes |
Electrical Characteristics
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Characteristic Impedence | Max. Current |
---|---|---|---|
6.4 Ohms/1000ft | 14.5 pF/ft (47.6 pF/m) | 100 Ohm | 6.3 Amps per Conductor at 25ºC |
UL Voltage Rating |
---|
300 V |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
75°C | -5°C to +75°C |
Stationary Min. |
---|
2.0 in (51 mm) |
Max. Pull Tension: | 39 lbs (18 kg) |
Bulk Cable Weight: | 25 lbs/1000ft (37 kg/km) |
Standards and Compliance
Environmental Suitability: | Indoor, Indoor |
Flammability / Reaction to Fire: | UL 1685 |
CPR Compliance: | CPR Euroclass: Eca |
NEC / UL Compliance: | Article 760, FPL |
European Directive Compliance: | EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
Plenum Number: | 6320UJ |
History
Update and Revision: | Revision Number: 0.11 Revision Date: 02-21-2024 |