Product Overview
Suitable Applications: | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
Construction Details
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 4 | 18 AWG | Solid | BC – Bare Copper |
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC – Polyvinyl Chloride | 0.01 in (0.25 mm) | 0.061 in (1.5 mm) | Black, Red, Brown, Blue |
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (Solid) TC |
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.18 in | Yes |
Overall Cable Diameter (Nominal): | 0.18 in |
Electrical Characteristics
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Max. Current |
---|---|---|---|
6.65 Ohm/1000ft | 40 pF/ft (130 pF/m) | 72 pF/ft (240 pF/m) | 4 Amps per Conductor at 25ºC |
UL Voltage Rating |
---|
300 V |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
75°C | 0°C To +75°C |
Stationary Min. | Installation Min. |
---|---|
2.7 in (69 mm) | 2.7 in |
Max. Pull Tension: | 83.5 lbs (37.9 kg) |
Bulk Cable Weight: | 32 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor |
Flammability / Reaction to Fire: | NFPA 262 (UL910) |
NEC / UL Compliance: | Article 760, FPLP |
European Directive Compliance: | EU CE Mark |
Other Standard Compliance(s): | California State Fire Marshall |
Non-Plenum Number: | 5322FL |
History
Update and Revision: | Revision Number: 0.312 Revision Date: 05-05-2023 |
Part Numbers
Item # | Color | UPC | Footnote |
---|---|---|---|
6322FL 0021000 | Red | 612825175957 | C |