Product Overview
Suitable Applications: | Instrumentation and computer cable for data transmission applications |
Physical Characteristics (Overall)
AWG | Stranding | Material |
---|---|---|
16 | 19×29 | TC – Tinned Copper |
Conductor Count: | 2 |
Total Number of Pairs: | 1 |
Material | Nominal Diameter | Diameter +/- Tolerance |
---|---|---|
PE – Polyethylene | 3.1 mm | 0.07 mm |
Number | Color |
---|---|
Wire 1 | Black |
Wire 2 | Transparent |
Type | Material | Drainwire Material | Drainwire AWG |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | TC – Tinned Copper | 18 |
Material | Color | Nominal Diameter |
---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | Chrome | 8.1 mm |
Material |
---|
Bi-Laminate (Alum+Poly) |
Material | Nominal Diameter | Nominal Wall Thickness |
---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | 12.5 mm | 1.3 mm |
Construction and Dimensions
Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
---|---|---|---|
Steel Wire Armoring | Single steel wire | 0.9 mm | 95% |
Electrical Characteristics
Nominal Conductor DCR | Nominal Outer Shield DCR |
---|---|
14.76 Ohm/km | 20 Ohm/km |
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Shield |
---|---|
75.4 pF/m | 144.4 pF/m |
Nominal Pair Inductance |
---|
0.66 µH/m |
Max. Recommended Current [A] |
---|
7 A |
Temperature Range
Installation Temperature Range: | -15°C To +80°C |
Storage Temperature Range: | -15°C To +80°C |
Operating Temperature Range: | -15°C To +80°C |
Operating Temp Range (Fixed Install): | -45°C To +80°C |
Mechanical Characteristics
Oil Resistance: | IEC 60811-404 |
Bulk Cable Weight: | 300 kg/km |
Standards
CPR Euroclass: | Dca-s1,d2,a1 |
Applicable Environmental and Other Programs
Environmental Space: | Indoor, Indoor/Outdoor, Outdoor, Indoor/Outdoor – Euroclass Dca |
Flammability, LS0H, Toxicity Testing
IEC Flammability: | IEC 60332-1-2, IEC 60332-3-24 |
IEC 60754-1 – Halogen Amount: | Zero |
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: | 2.5 µS/mm |
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: | 4.3 |