Product Overview
Suitable Applications: | RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, …); Low Voltage Digital Control (24v, ); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc. |
Construction Details
Size | Stranding | Material |
---|---|---|
24 | 7×32 | TC – Tinned Copper |
Material | Nom. Insulation Diameter | Color Code |
---|---|---|
PE – Polyethylene | 1.73 mm (0.0681 in) | White/Blue & Blue/White |
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 24 AWG (7×32) TC |
Braid | Tinned Copper (TC) | 90% |
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | 0.9 mm (0.035 in) | 6.10 mm (0.240 in) |
Table Notes: | UV Stabilised |
Overall Cable Diameter (Nominal): | 6.10 mm (0.240 in) |
Electrical Characteristics
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|---|---|---|---|---|
78.7 Ohm/km (24.0 Ohm/1000ft) | 42 pF/m (13 pF/ft) | 75.5 pF/m | 120 Ohm | 66% | 2.1 Amps per Conductor |
Nom. Outer Shield DCR: | 11.0 Ohm/km (3.35 Ohm/1000ft) |
Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
---|---|
1 | 1.97 dB/100m |
Mechanical Characteristics
Operating | Installation | Storage |
---|---|---|
-45°C To +80°C | -15°C To +80°C | -45°C To +80°C |
Stationary Min. | Installation Min. |
---|---|
30 mm (1.2 in) | 61 mm (2.4 in) |
Max. Pull Tension: | 328 N (73.7 lbf) |
Bulk Cable Weight: | 33 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor – Euroclass Dca, Indoor, Non-Halogenated, Sunlight Resistance, Oil Resistance |
Flammability / Reaction to Fire: | IEC 60332-3-22, IEC 60332-3-24 |
CPR Compliance: | CPR Euroclass: Dca-s2,d1,a1; CPR UKCA Class: Dca-s2,d1,a1 |
ISO/IEC Compliance: | IEC 61034-2 – Smoke Density Min Transmittance = 60% |
CENELEC Compliance: | EN 50290-2-20 |
European Halogen Free Standards: | IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 – Halogen Amount = Zero, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 2.5 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3 |
European Directive Compliance: | EU CE Mark |
UK Regulation Compliance: | UKCA Mark |
Other Standard Compliance(s): | DMX-512 |
History
Update and Revision: | Revision Number: 0.669 Revision Date: 02-15-2024 |
Part Numbers
Item # | Color | Putup Type | Length | UPC/EAN | Footnote |
---|---|---|---|---|---|
9841NH.00152 | Chrome | Reel | 152 m | 8719605022929 | |
9841NH.00305 | Chrome | Reel | 305 m | 8719605022936 | |
9841NH.K0305 | Chrome | Reel | 305 m | 8719605177629 | |
9841NH.00500 | Chrome | Reel | 500 m | 8719605022943 | |
9841NH 0601000 | Chrome | Reel | 1,000 ft | 612825259497 | C |
9841NH 0601000 | Chrome | Reel | 1,000 ft | 612825259497 | C |
9841NH.001000 | Chrome | Reel | 1,000 m | 8719605022912 |