Product Description
Brand: | Belden |
Product Family: | I/O Systems: Active – Standalone |
Product Sub Family: | LioN-X |
Item Description: | 0980 XSL 3900-121-007D-01F |
Part Number: | 935705001 |
Product Life Cycle
Device Type: | I/O Device |
Protocol: | Multiprotocol |
I/O Function: | 16DIO |
Power Connection (System Supply): | M12 Power, 5-poles, L-coded |
I/O Connection: | M12, 5-poles, A-coded |
I/O Type: | Digital In-/Output (Universal) |
General Data
Housing Material: | Metal, zinc die-cast |
Housing Plating: | Nickel, matt |
Housing Color: | Grey Metallic |
Protection Degree / IP Rating**: | IP65, IP67, IP69K |
Potted: | Yes |
Dimensions (W x H x D): | 60 mm x 31 mm x 200 mm |
Weight: | 480 g |
Ambient Temperature (Operation)*: | -40 °C to 70 °C |
Ambient Temperature (Storage/Transport): | -40 °C to 70 °C |
Permissible Humidity (Operation): | 5 % … 95 % (For UL applications max. 80 %) |
Permissible Humidity (Storage/Transport): | 5 % … 95 % (For UL applications max. 80 %) |
Air Pressure (Operation): | 80 kPa 106 kPa (up to 2000 m above sea level) |
Air Pressure (Storage/Transport): | 80 kPa 106 kPa (up to 2000 m above sea level) |
Flammabilty Class: | UL 94 (IEC 61010) |
Protection Class: | III, IEC 61140, EN 61140, VDE 0140-1 |
Pollution Degree: | 3 acc. to EN 60664-1, VDE 0110-1 |
Vibration Resistance: | 15 g / 5 -500 Hz |
Shock Resistance: | 50 g / 11ms |
Contact Base Material: | M12, D-coded, CuSn, Gold-plated | M12 Power, L-coded, CuNi, Gold-plated |
Contact Bearer Material: | PA / TPU |
O-Ring Material: | FKM |
Mounting: | 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts. |
Fastening Torque (Fixing Screw): | M4: 1 Nm |
Fastening Torque (Ground Connection (FE)): | M4: 1 Nm |
Fastening Torque (Bus Connection): | M12: 0.5 Nm |
Fastening Torque (Power Connection): | M12: 0.5 Nm |
Fastening Torque (I/O Connection): | M12: 0.5 Nm |
Included in Delivery: | Attachable Labels: 15x, Sealing Caps: 5x M12 |
Accessories to Order Separately: | Ethernet cable, mounting adapter, sensor/actuator cable, power cable |
PROFINET
Protocol: | PROFINET |
Connection: | M12 4-poles, D-coded |
Number of Connections: | 2 |
Specification: | V2.3 |
Conformance Class: | C (CC-C) |
Performance Class: | RT (switch supports IRT) |
Netload Class: | III |
Transmission Rate: | Fast Ethernet (10/100 Mbit/s), Full Duplex |
Transmission Method: | 100 BASE-TX, with auto negotiation and auto crossing |
Cycle Time / Update Rate: | min. 1 ms |
Addressing: | DCP |
Media Redundancy Protocol (MRP): | Supported, MRP client |
Shared Device: | Supported |
Shared Input: | not supported |
Topology Detection: | LLDP, SNMP V3 |
Easy Device Replacement: | Supported, based on LLDP |
Supported Network Protocols (Other): | ARP, HTTP, Ping, SNMP V1, TCP/IP |
EtherNet/IP
Protocol (EtherNet/IP): | EtherNet/IP |
Connection: | M12, 4-poles, D-coded |
Number of Connections: | 2 |
Specification: | CIP V3.2x, EIP Adaption of CIP V1.2x |
Transmission Rate: | Fast Ethernet (10/100 Mbit/s), Full Duplex |
Transmission Method: | 100 BASE-TX, with auto negotiation and auto crossing |
Cycle Time / Requested Packet Interval (RPI): | min. 1 ms |
Addressing: | BootP, DHCP, Rotary Address Switches |
Address Switches Range: | 0 to 255 dec |
Connection Types: | Exclusive Owner, Input Only, Listen Only |
CIP Msg Connection Limit: | 6 |
CIP I/O Connection Limit: | 3 |
Device Level Ring (DLR): | Supported, beacon based |
Quick Connect (QC): | Supported, ? 500 ms |
Supported Network Protocols (Other): | ACD, ARP, BootP, DHCP, HTTP, IGMP, Ping, TCP/IP |
EtherCAT
Protocol: | EtherCAT |
Connection: | M12 4-poles, D-coded |
Number of Connections: | 2 |
Specification: | ETG.1000 V1.2 |
Transmission Rate: | Fast Ethernet (10/100 Mbit/s), Full Duplex |
Transmission Method: | 100 BASE-TX, with auto negotiation and auto crossing |
Cycle Time / Update Rate: | min. 250 µs |
Addressing: | Auto-increment addressing, fixed position addressing |
Mailbox Protocols: | CANopen over EtherCAT (CoE), File access over EtherCAT (FoE), Ethernet over EtherCAT (EoE) |
Supported Network Protocols (Other): | Over EoE: HTTP, Ping, TCP/IP |
CC-Link IE Field Basic
Protocol: | CC-Link IE Field Basic |
Connection: | M12 LAN, 4-poles. D-coded |
Number of Connections: | 2 |
Specification: | v2 |
Transmission Rate: | Fast Ethernet (100 Mbit/s), Full Duplex |
Transmission Method: | 100 BASE-TX, with auto negotiation and auto crossing |
Cycle Time / Update Rate: | min 1ms |
Address Switches Range: | 0 to 99 dec |
Number of stations: | 4 |
Supported Network Protocols: | SNMP, ACD, ARP, HTTP, IGMP, Ping, TCP/IP |
Supported IIoT Protocols: | OPC UA, MQTT, CoAP, Syslog, Node Red |
Modbus TCP
Protocol: | Modbus TCP |
Connection: | M12, 4-poles, D-coded |
Number of Connections: | 2 |
Device Type: | Modbus Slave |
Specification: | Modbus application protocol V1.1b |
Supported Network Protocols: | SNMP V1, HTTP, TFTP, FTP, BootP, DHCP |
IIoT Protocols
OPC UA: | Cyclic data read/write, Diagnosis data, Event data |
MQTT: | Cyclic data read/write, Diagnosis data, Event data |
REST API: | Cyclic data read/write, Diagnosis data, Event data |
CoAP: | Cyclic data read/write, Diagnosis data, Event data |
Power Supply
Connection Module Supply Voltage: | M12 Power, 5-poles, L-coded |
Number of Connections: | 2 |
Current Carrying Capacity of Connector: | max. 16 A |
Module Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Module Supply Voltage (Range): | 18 V DC to 30 V DC |
Current Consumption (typ.): | 160 mA (at 24 V DC) |
Reverse Polarity Protection: | Yes |
Status Indicator (System Supply): | LED green |
Diagnostic Indicator: | LED red |
Connection Sensor Supply Voltage: | M12 Power, 5-poles, L-coded |
Current Carrying Capacity of Connector: | max. 16 A |
Sensor Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Sensor Supply Voltage (Range): | 18 V DC to 30 V DC |
Reverse Polarity Protection: | Yes |
Status Indicator (Sensor Supply): | LED green |
Diagnostic Indicator: | LED red |
Current Carrying Capacity of Connector: | max. 16 A |
Actuator Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Actuator Supply Voltage (Range): | 18 V DC to 30 V DC |
Reverse Polarity Protection: | Yes |
Status Indicator (Actuator Supply): | LED green |
Diagnostic Indicator: | LED red |
Digital Input Channels
Number of Digital Input Channels: | up to 16 |
Connection: | M12, 5-poles, A-coded |
Number of Ports: | 8x, X1 to X8 |
Channel Type: | Type 3 acc. to IEC 61131-2 |
Input Wiring: | 2-, 3-, 4-wire |
Nominal Voltage: | 24 V DC via US (module power supply) |
Nominal Current: | typ. 5 mA |
Sensor Current Supply: | max. 4A per port |
Sensor Type: | PNP |
Input Voltage Range “0” signal: | -3 V DC +5 V DC |
Input Voltage Range “1” signal: | 11 V DC 30 V DC |
Protective Circuit: | Electronically: Overload protection, short-circuit protection |
Status Indicator (Inputs): | LED white or yellow per channel |
Diagnostic Indicator: | LED red per port |
Digital Output Channels
Number of Digital Output Channels: | up to 16 |
Connection: | M12, 5-poles, A-coded |
Number of Ports: | 8x, X1 to X8 |
Channel Type: | p-switching |
Output Wiring: | 2-wire |
Nominal Voltage: | 24 V DC via UL |
Output Current per Channel: | max. 2 A |
Output Current per Module: | max. 16 A (for UL compliance: max 9A) |
Galvanically Isolated: | No |
Protective Circuit: | Electronically: Overload protection, short-circuit protection |
Overload Behavior: | Auto off and on switching / Manual restart |
Status Indicator (Outputs): | LED white or yellow per channel |
Diagnostic Idicator: | LED red per channel |
Electrical Isolation
US (System Supply Voltage) / FE: | 500 V DC |
UL / FE: | 500 V DC |
Bus connection / FE: | 2000 V DC |
EMC Conformance
EMC Directive: | 2014/30/EU |
EN 61000-4-2 Electrostatic Discharge (ESD): | Criterion B; 4 kV contact discharge, 8 kV air discharge |
EN 61000-4-3 Electromagnetic Field: | Criterion A; Field intensity: 10 V/m |
EN 61000-4-4 Fast Transients (Burst): | Criterion B, 2 kV |
EN 61000-4-5 Surge Voltage: | Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ? 30m |
EN 61000-4-6 Conducted immunity: | Criterion A; Test voltage 10 V |
EN 55032 Radio Interference Properties: | Class A |
Safety & Environmental Compliance
CE: | Yes |
RoHS Compliant: | Yes |
China RoHS-Compliant: | Yes |
Approvals
UL: | cULus Listed, UL 61010-1 |
CSA: | Yes, via UL |
PNO: | Yes |
ODVA: | Yes |
ETG: | Yes |
Notes
Protection Degree / IP Rating Note: | *only if mounted and locked in combination with Hirschmann / Lumberg Automation connector. |
System Power Supply Connection Note: | *do not connect / disconnect under voltage! |
Item # | Item Description |
---|---|
935705001 | 0980 XSL 3900-121-007D-01F |
Update and Revision: | Revision Number: 0.25 Revision Date: 07-20-2023 |