Product Overview
Suitable Applications: | Horizontal and building backbone cable; Support current and future Category 6a, 7 and 7a applications, such as: 10GBase – T (10 Gigabit Ethernet), 1000Base – T (Gigabit Ethernet), 100 Base – T, 10 Base – T, FDDI, ATM |
Construction Details
Element | Size | Stranding | Material | No. of Pairs | No. of Elements |
---|---|---|---|---|---|
Individual Shielded Pair | 23 AWG | Solid | BC – Bare Copper | 8 | 16 |
Element | Material | Nom. Insulation Diameter | Color Code |
---|---|---|---|
Individual Shielded Pair | PE – Polyethylene (Foam) | 1.42 mm (0.0559 in) | White & Blue, White & Orange, White & Green, White & Brown |
Description |
---|
4 pairs twisted together |
Element | Shield Type | Material | Coverage |
---|---|---|---|
Individual Shielded Pair | Tape | Bi-Laminate (Alum+Poly) | 100% |
Table Notes: | Aluminum facing outside |
Shield Type | Material | Coverage |
---|---|---|
Braid | Tinned Copper (TC) | 30% |
Material | Nom. Diameter | Ripcord |
---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | 7.5 mm (0.30 in) | Yes |
Table Notes: | Figure 8 construction |
Overall Cable Diameter (Nominal): | 7.5 mm (0.30 in) |
Electrical Characteristics
Max. Conductor DCR | Max. Mutual Capacitance | Max. Capacitance Unbalance | Nom. Characteristic Impedance |
---|---|---|---|
95 Ohm/km | 56 pF/m (17 pF/ft) | 160 pF/100m | 100 Ohm |
Max. Delay Skew | Nom. Velocity of Prop. |
---|---|
25 ns/100m | 76% |
Frequency [MHz] | Max. Insertion Loss (Attenuation) | Min. NEXT [dB] | Min. PSNEXT [dB] | Min. ACR [dB] | Min. PSACR [dB] | Min. ACRF (ELFEXT) [dB] | Min. PSACRF (PSELFEXT) [dB] | Min. RL (Return Loss) [dB] | Min. PSANEXT [dB] | Min. PSAACRF [dB] | Min. TCL [dB] | Min. ELTCTL [dB] |
---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 2.1 dB/100m | 78 | 75 | 75.9 | 72.9 | 78 | 75 | 20 | 67 | 67 | 40 | 23 |
4 | 3.7 dB/100m | 78 | 75 | 74.3 | 71.3 | 78 | 75 | 23 | 67 | 67 | 34 | 15 |
10 | 5.8 dB/100m | 78 | 75 | 72.2 | 69.2 | 75.3 | 72.3 | 25 | 67 | 67 | 30 | 10.9 |
16 | 7.3 dB/100m | 78 | 75 | 70.7 | 67.7 | 71.2 | 68.2 | 25 | 67 | 67 | 28 | 5.1 |
31.2 | 10.3 dB/100m | 78 | 75 | 67.7 | 64.7 | 65.4 | 62.4 | 23.6 | 67 | 63.3 | 25.2 | |
62.5 | 14.6 dB/100m | 78 | 75 | 63.4 | 60.4 | 59.4 | 56.4 | 21.5 | 67 | 57.3 | 22 | |
100 | 18.5 dB/100m | 75.4 | 72.4 | 56.9 | 53.9 | 55.3 | 52.3 | 20.1 | 67 | 53.2 | 20 | |
155 | 23.2 dB/100m | 72.5 | 69.5 | 49.3 | 46.3 | 51.5 | 48.5 | 18.8 | 67 | 49.4 | 18.1 | |
250 | 29.7 dB/100m | 69.4 | 66.4 | 39.7 | 36.7 | 47.3 | 44.3 | 17.3 | 67 | 45.2 | 16 | |
500 | 42.8 dB/100m | 64.9 | 61.9 | 22.2 | 19.2 | 41.3 | 38.3 | 17.3 | 67 | 39.2 | ||
600 | 47.1 dB/100m | 63.7 | 60.7 | 16.6 | 13.6 | 39.7 | 36.7 | 17.3 | 65.8 | 37.6 | ||
1000 | 61.9 dB/100m | 60.4 | 57.4 | 35.3 | 32.3 | 15.1 | 62.5 | 33.2 | ||||
1200 | 68.4 dB/100m | 59.2 | 55.9 | 33.7 | 30.7 | 14.1 | 61.3 | 31.6 |
Table Notes: | Limits below 4 MHz are for information only; Values at 1200 MHz are for information only. Reference standard: IEC 61156-5 |
Frequency | Max. Transfer Impedance |
---|---|
1 Mhz | Max. 50 mOhm/m |
10 Mhz | Max. 100 mOhm/m |
30 Mhz | Max. 200 mOhm/m |
100 Mhz | Max. 1000 mOhm/m |
Transfer Impedance Class: | Grade 2 |
Screening Class: | Type Ib |
Table Notes: | Coupling Attenuation |
Voltage Rating |
---|
72 V DC |
Mechanical Characteristics
Operating | Installation |
---|---|
-30°C to +60°C | 0°C To +50°C |
Stationary Min. | Installation Min. |
---|---|
32 mm (1.3 in) | 64 mm |
Max. Pull Tension: | 85 N (19 lbf) |
Bulk Cable Weight: | 110 kg/km |
Standards and Compliance
Environmental Suitability: | Indoor – Euroclass Dca |
Flammability / Reaction to Fire: | IEC 60332-1-2 |
CPR Compliance: | CPR Euroclass: Dca-s1,d1,a1 |
IEEE Compliance: | PoE: IEEE 802.3bt Type 1, Type 2, Type 3, Type 4 |
Data Category: | Category 7A |
TIA/EIA Compliance: | ANSI/TIA 568.2-D |
ISO/IEC Compliance: | ISO/IEC 11801-1, IEC 61034-2 – Smoke Density Min Transmittance = 60% |
CENELEC Compliance: | EN 50173-1, Segregation class according EN50174-2 = d |
European Halogen Free Standards: | IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 – Halogen Amount = Zero, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 2.5 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3 |
European Directive Compliance: | EU CE Mark |
UK Regulation Compliance: | UKCA Mark |
Product Notes
Notes: | Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. |
History
Update and Revision: | Revision Number: 0.309 Revision Date: 12-12-2023 |
Part Numbers
Item # | Color | Putup Type | Length | EAN |
---|---|---|---|---|
1889ENH.00500 | Gray, RAL 7032 | Reel | 500 m | 8719605161970 |