, , ,

29722C – VFD, 3C #12 Str BC XLPE Ins + #12 Symm. Seg. Gnd (3 of #16) Str BC, CTS, Blk PVC Jkt, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements

Construction Details

Conductor
Element No. of Elements Size Stranding Material Notes
Conductor(s) 3 12 AWG 7×20 BC – Bare Copper
Ground 3 16 AWG 7×24 BC – Bare Copper Segmented Grounds
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) XLPE – Cross-Linked Polyethylene (Thermoset) 0.063 in (1.6 mm) 0.219 in (5.56 mm) Black and Numbered
Ground No Insulation
Outer Shield
Shield Type Material Coverage
Helical Tape Bare Copper (BC) 100%
Helical Tape Bare Copper (BC) 100%
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.063 in (1.6 mm) 0.610 in (15.5 mm) Yes
Overall Cable Diameter (Nominal): 0.610 in (15.5 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Conductor(s) 1.42 Ohm/1000ft (4.66 Ohm/km) 40 pF/ft (130 pF/m) 72 pF/ft (240 pF/m) 46 Ohm 55% 30 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
2000 V (TC), 1000 V (CSA AWM I/II A/B)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -40°C To +90°C
Bend Radius
Stationary Min. Installation Min.
7.3 in (190 mm) 7.3 in (190 mm)
Max. Pull Tension: 367 lbs (166 kg)
Bulk Cable Weight: 237 lbs/1000ft (353 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: UL1685 UL Loading, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL Compliance: Article 336, TC-ER, RHW-2
AWM Compliance: I/II A/B
ICEA Compliance: S-95-658
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): P-07-KA070003-MSHA

History

Update and Revision: Revision Number: 0.70 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Putup Type UPC
29722C 0102500 Reel 612825445456
29722C 0105000 Reel 612825445463
SKU: 29722C Categories: , , ,

You were not leaving your cart just like that, right?

Enter your details below to save your shopping cart for later. And, who knows, maybe we will even send you a sweet discount code :)