5220UJ – Fire Alarm, #16-2c BC, FPL


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Fire Alarm, Addressable Systems, Circuits: Audio, Control, Initiating, Notification

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 16 AWG Solid BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code Notes
Pair(s) PE – Polyethylene (Foam) 0.015 in (0.38 mm) 0.082 in (2.1 mm) Black & Red HDPE
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.033 in (0.84 mm) 0.23 in Yes
Overall Cable Diameter (Nominal): 0.23 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Max. Current
3.9 Ohm/1000ft 13 pF/ft (43 pF/m) 6.3 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C -20°C To +75°C
Bend Radius
Stationary Min. Installation Min.
1.84 in (46.7 mm) 1.84 in
Max. Pull Tension: 62.4 lbs (28.3 kg)
Bulk Cable Weight: 29 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor (Not Riser or Plenum), Indoor
Flammability / Reaction to Fire: UL1685 UL Loading
CPR Compliance: CPR Euroclass: Eca
NEC / UL Compliance: Article 760, FPL
European Directive Compliance: EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation Compliance: UKCA Mark
APAC Compliance: China RoHS II (GB/T 26572-2011)
Plenum Number: 6220UJ

History

Update and Revision: Revision Number: 0.316 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Color UPC Footnote
5220UJ 0021000 Red 612825158363 C