558AM1 – Indoor/Outdoor Access Control CM Rated Composite


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Indoor/Outdoor: Access Control, Security System, Power Limited Controls

Construction Details

Conductor
Element Description Element No. of Elements Size Stranding Material
Card Reader Conductor(s) 6 22 AWG 7×30 BC – Bare Copper
Door Contact Conductor(s) 2 22 AWG 7×30 BC – Bare Copper
REX/Spare Conductor(s) 4 22 AWG 7×30 BC – Bare Copper
Lock Power Conductor(s) 4 18 AWG 7×26 BC – Bare Copper
Insulation
Element Description Element Material Nom. Thickness Color Code
Card Reader Conductor(s) PVC – Polyvinyl Chloride .010 in (0.25 mm) Black, Red, White, Green, Brown, Blue
Door Contact Conductor(s) PVC – Polyvinyl Chloride .010 in (0.25 mm) Black, Red
REX/Spare Conductor(s) PVC – Polyvinyl Chloride .010 in (0.25 mm) Black, Red, White, Green
Lock Power Conductor(s) PVC – Polyvinyl Chloride .012 in (0.30 mm) Black, Red, White, Green
Inner Shield
Element Description Element Shield Type Material Coverage Drainwire Type
Card Reader Conductor(s) Tape Bi-Laminate (Alum+Poly) 100% 24 AWG (7×32) TC
Door Contact Conductor(s) No Shield
REX/Spare Conductor(s) No Shield
Lock Power Conductor(s) No Shield
Waterblocking: Waterblock Tape
Inner Jacket
Element Description Element Separator Material Nom. Thickness Nom. Diameter Ripcord Color
Card Reader Conductor(s) Waterblocking Tape PVC – Polyvinyl Chloride .025 in (0.64 mm) .226 in (5.74 mm) Yes Orange
Door Contact Conductor(s) Waterblocking Tape PVC – Polyvinyl Chloride .025 in (0.64 mm) .168 in (4.27 mm) Yes White
REX/Spare Conductor(s) Waterblocking Tape PVC – Polyvinyl Chloride .025 in (0.64 mm) .187 in (4.75 mm) Yes Blue
Lock Power Conductor(s) Waterblocking Tape PVC – Polyvinyl Chloride .025 in (0.64 mm) .233 in (5.92 mm) Yes Gray
Outer Jacket
Material Nom. Diameter
PVC – Polyvinyl Chloride .565 in (14.4 mm)
Overall Cable Diameter (Nominal): .565 in (14.4 mm)

Electrical Characteristics

Electricals
Element Description Element Max. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield)
Card Reader Conductor(s) 16.3 Ohm/1000ft (53.5 Ohm/km) 55 pF/ft (180 pF/m) 99 pF/ft (320 pF/m)
Door Contact Conductor(s) 16.3 Ohm/1000ft (53.5 Ohm/km) 27 pF/ft (89 pF/m)
REX/Spare Conductor(s) 16.3 Ohm/1000ft (53.5 Ohm/km) 27 pF/ft (89 pF/m)
Lock Power Conductor(s) 6.5 Ohm/1000ft (21 Ohm/km) 34 pF/ft (110 pF/m)
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
60°C -20°C to +60°C
Bend Radius
Stationary Min. Installation Min.
5.6 in (140 mm) 5.6 in (140 mm)

Standards and Compliance

Environmental Suitability: Indoor/OutdoorIndoor Rated (Not Riser or Plenum)
Flammability / Reaction to Fire: UL 1685
CPR Compliance: CPR Euroclass: Eca
NEC / UL Compliance: Article 800, CM
European Directive Compliance: EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Plenum Number: 658AMJ

History

Update and Revision: Revision Number: 0.24 Revision Date: 03-07-2024