Product Overview
Suitable Applications: | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
Physical Characteristics (Overall)
AWG | Stranding | Material | No. of Conductors |
---|---|---|---|
22 | Solid | BC – Bare Copper | 6 |
Conductor Count: | 6 |
Material | Material Trade Name | Nominal Wall Thickness |
---|---|---|
PVC – Polyvinyl Chloride | Flamarrest® | 0.009 in |
Number | Color |
---|---|
1 | Black |
2 | Red |
3 | Brown |
4 | Blue |
5 | Orange |
6 | Yellow |
Material |
---|
No Shield |
Material | Material Trade Name | Nominal Diameter | Nominal Wall Thickness | Ripcord |
---|---|---|---|---|
PVC – Polyvinyl Chloride | Flamarrest® | 0.162 in | 0.015 in | Yes |
Electrical Characteristics
Nominal Conductor DCR |
---|
15.7 Ohm/1000ft |
Nom. Capacitance Conductor to Conductor |
---|
25 pF/ft |
Max. Recommended Current [A] |
---|
2 Amps per Conductor at 25ºC |
UL Voltage Rating |
---|
300 V RMS |
Temperature Range
UL Temp Rating: | 75°C |
Operating Temperature Range: | 0°C To +75°C |
Mechanical Characteristics
Bulk Cable Weight: | 20.8 lbs/1000ft |
Max. Pull Tension: | 46.8 lbs |
Min. Bend Radius/Minor Axis: | 1.6 in |
Standards
NEC Articles: | Article 760 |
NEC/(UL) Compliance: | FPLP |
Other Specification: | California State Fire Marshall |
Applicable Environmental and Other Programs
EU Directive Compliance: | EU Directive 2003/11/EC (BFR) |
EU CE Mark: | Yes |
MII Order #39 (China RoHS): | Yes |
Flammability, LS0H, Toxicity Testing
UL Flammability: | NFPA 262 Plenum Flame Test (UL910) |
UL voltage rating: | 300 V RMS |
Plenum/Non-Plenum
Plenum (Y/N): | Yes |
Related Part Numbers
Non-Plenum Number: | 5524UL |
Item # | Color | UPC |
---|---|---|
6524UL 002C500 | Red | 612825178194 |
History
Update and Revision: | Revision Number: 0.297 Revision Date: 05-05-2023 |