Product Overview
Suitable Applications: | low voltage analog signals (4-20ma, 0-10v, …); low voltage control (24v, ); line level audio; voice communications; panel wiring |
Construction Details
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 2 | 22 | 7×30 | TC – Tinned Copper |
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.60 in (15 mm) | Black, Red, White |
Shield Type | Material | Coverage |
---|---|---|
Braid | Tinned Copper (TC) | 80% |
Shield Type | Material | Coverage |
---|---|---|
Braid | Tinned Copper (TC) | 90% |
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
PVC – Polyvinyl Chloride | 0.025 in (0.64 mm) | 0.194 in |
Electrical Characteristics
Nom. Conductor DCR | Max. Conductor DCR | Max. Current |
---|---|---|
10 Ohm/1000ft | 15 Ohm/1000ft (49 Ohm/km) | 2.9 Amps per Conductor at 25ºC |
UL Voltage Rating |
---|
300 V |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
60°C | -20°C To +60°C |
Stationary Min. | Installation Min. |
---|---|
1.94 in (49.3 mm) | 1.94 in |
Max. Pull Tension: | 18 lbs (8.2 kg) |
Bulk Cable Weight: | 22 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor |
Flammability / Reaction to Fire: | UL1685 UL Loading, IEC 60332-1-2 |
CPR Compliance: | CPR Euroclass: Eca |
NEC / UL Compliance: | Article 800, CM |
AWM Compliance: | AWM 2785 |
European Directive Compliance: | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
UK Regulation Compliance: | UKCA Mark |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
Product Notes
Notes: | Inner Shield over white conductor only. |
History
Update and Revision: | Revision Number: 0.528 Revision Date: 11-30-2023 |
Part Numbers
Item # | Color | Putup Type | Length | UPC | Footnote |
---|---|---|---|---|---|
8734 0601000 | Chrome | Reel | 1,000 ft | 612825214779 | C |