8761NH – Electronic, 2 C #22 Str TC, PE ins, OS, LSZH Jkt, 300V, Dca


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: low voltage analog signals (4-20ma, 0-10v, …); low voltage digital control (24v, …); line level audio; computer communication; panel wiring

Construction Details

Conductor
Size Stranding Material
22 7×30 TC – Tinned Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PE – Polyethylene 0.017 in (0.43 mm) 1.57 mm (0.0618 in) Black & Clear
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter
LSZH – Low Smoke Zero Halogen (Flame Retardant) 0.9 mm (0.035 in) 4.95 mm (0.195 in)
Overall Cable Diameter (Nominal): 4.95 mm (0.195 in)

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
52.5 Ohm/km (16.0 Ohm/1000ft) 78.7 pF/m (24.0 pF/ft) 154.2 pF/m (47.00 pF/ft) 64 Ohm 66% 2.9 Amps per Conductor

Mechanical Characteristics

Temperature
Operating Installation Storage
-45°C To +80°C -15°C To +80°C -45°C To +80°C
Bend Radius
Installation Min.
49.5 mm (1.95 in)
Max. Pull Tension: 158 N (35.5 lbf)
Bulk Cable Weight: 15 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor – Euroclass Dca, Indoor, Non-Halogenated, Sunlight Resistance
Flammability / Reaction to Fire: IEC 60332-1-2, IEC 60332-3-24
CPR Compliance: CPR Euroclass: Dca-s2,d1,a1; CPR UKCA Class: Dca-s2,d1,a1
ISO/IEC Compliance: IEC 61034-2 – Smoke Density Min Transmittance = 60%
CENELEC Compliance: EN 50290-2-20
European Halogen Free Standards: IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 – Halogen Amount = Zero, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 2.5 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2)
UK Regulation Compliance: UKCA Mark

History

Update and Revision: Revision Number: 0.334 Revision Date: 03-15-2024

Part Numbers

Variants
Item # Color Putup Type Length EAN
8761NH.00305 Chrome Reel 305 m 8719605019011
8761NH.00500 Chrome Reel 500 m 8719605019028
8761NH.001000 Chrome Reel 1,000 m 8719605019004
8761NH.01305 White Reel 305 m 8719605174611