Product Overview
Suitable Applications: | fire alarms; indoor applications; low voltage analog signals (4-20ma, 0-10v, …); low voltage control (24v, ) |
Construction Details
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 6 | 22 AWG | Solid | TC – Tinned Copper |
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC – Polyvinyl Chloride | 0.013 in (0.33 mm) | 0.052 in (1.3 mm) | Black, White, Red, Green, Brown, Blue |
Material |
---|
No Shield |
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
PVC – Polyvinyl Chloride | 0.039 in (0.99 mm) | 0.234 in |
Overall Cable Diameter (Nominal): | 0.234 in |
Electrical Characteristics
Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|---|---|---|
Conductor(s) | 20 Ohm/1000ft | 25.5 pF/ft (83.7 pF/m) | 3.5 Amps per Conductor at 25ºC |
UL Voltage Rating |
---|
300 V |
Mechanical Characteristics
UL Temperature | Operating |
---|---|
105°C | -40°C To +105°C |
Stationary Min. | Installation Min. |
---|---|
2.34 in (59.4 mm) | 2.34 in |
Max. Pull Tension: | 46.8 lbs (21.2 kg) |
Bulk Cable Weight: | 33 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance |
Flammability / Reaction to Fire: | UL1666 Riser, FT4, IEC 60332-1-2 |
CPR Compliance: | CPR Euroclass: Eca |
NEC / UL Compliance: | Article 760, Article 800, CMR, FPLR |
AWM Compliance: | AWM 2464 |
CEC / C(UL) Compliance: | CMG, FAS105 |
European Directive Compliance: | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
UK Regulation Compliance: | UKCA Mark |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
Other Standard Compliance(s): | California State Fire Marshall |
History
Update and Revision: | Revision Number: 0.393 Revision Date: 05-05-2023 |
Part Numbers
Item # | Color | UPC |
---|---|---|
9576 010U1000 | Black | 612825256182 |