Product Overview
Suitable Applications: | Instrumentation and computer cable; For data transmission applications |
Physical Characteristics (Overall)
AWG | Stranding | Material | No. of Pairs |
---|---|---|---|
24 | 7×32 | TC – Tinned Copper | 2 |
Conductor Count: | 4 |
Material | Material Trade Name | Nominal Diameter | Diameter +/- Tolerance |
---|---|---|---|
PE – Polyethylene (Foam) | Datalene® | 1.55 mm | 0.06 mm |
Number | Color |
---|---|
Pair 1 | Black & Red |
Pair 2 | Black & White |
Table Notes: | Shielded pairs |
Number | Color |
---|---|
Pair 1 | Red |
Pair 2 | Green |
Type | Material | Material Trade Name | Thickness of Foil | Drainwire Material | Drainwire AWG |
---|---|---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | Beldfoil® (Z-Fold®) | 9 / 12 µm | TC – Tinned Copper | AWG24/7 |
Material | Color | Nominal Diameter | Min. Wall Thickness | Min. Average Wall Thickness |
---|---|---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | Chrome (RAL 7037) | 7.9 mm | 0.91 mm | 1.10 mm |
Material |
---|
Bi-Laminate (Alum+Poly) |
Material | Nominal Diameter | Min. Wall Thickness | Nominal Wall Thickness |
---|---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | 12.5 mm | 1.25 mm | 1.35 mm |
Construction and Dimensions
Description | Filler |
---|---|
2 pairs and 2 fillers twisted to cable core | Polypropylene (Blue, 2.20 mm) |
Type of Armor | Material | Thickness of Armoring Wires | Coverage Percentage |
---|---|---|---|
Steel Wire Armoring | Galvanized steel wire | 0.9 mm | Min. 95% |
Electrical Characteristics
Nominal Conductor DCR | Nominal Inner Shield DCR |
---|---|
78.7 Ohm/km | 59.1 Ohm/km |
Nom. Capacitance Conductor to Conductor | Nom. Capacitance Conductor to Other Conductor to Shield |
---|---|
41 pF/m | 76.1 pF/m |
Nominal Pair Inductance |
---|
0.49 µH/m |
Nominal Characteristic Impedance |
---|
100 Ohm |
Frequency [MHz] | Nom. Insertion Loss |
---|---|
2 MHz | 4.63 dB/100m |
3 MHz | 5.35 dB/100m |
4 MHz | 5.91 dB/100m |
5 MHz | 6.5 dB/100m |
6 MHz | 6.89 dB/100m |
11 MHz | 9.15 dB/100m |
12 MHz | 9.51 dB/100m |
24 MHz | 13.16 dB/100m |
Element | Max. Recommended Current [A] |
---|---|
Conductor(s) | 1 A |
Voltage Rating [V] |
---|
300 V |
Temperature Range
Installation Temperature Range: | -15°C To +80°C |
Storage Temperature Range: | -45°C To +80°C |
Operating Temp Range (Flexible Install): | -15°C To +80°C |
Operating Temp Range (Fixed Install): | -45°C To +80°C |
Mechanical Characteristics
Oil Resistance: | IEC 60811-404 |
Min. Bend Radius During Installation: | 187.5 mm |
Standards
CENELEC Compliance: | EN 50290-2-20 |
Applicable Environmental and Other Programs
Environmental Space: | Indoor, Indoor/Outdoor, Outdoor, Indoor/Outdoor – Euroclass Eca |
Suitability
Suitability – Sunlight Resistance: | Yes |
Flammability, LS0H, Toxicity Testing
IEC Flammability: | IEC 60332-3-24 |
IEC 60754-1 – Halogen Amount: | Zero |
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: | 2.5 µS/mm |
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: | 4.3 |
IEC 61034-2 – Smoke Density Min. Transmittance: | 60% |
Related Part Numbers
Item # | Color | Put-Up Type | Length | EAN |
---|---|---|---|---|
9729LS.00500 | Black | Reel | 500 m | 8719605022516 |
9729LS.001000 | Black | Reel | 1,000 m | 8719605022509 |
9729LS.011000 | Black | Reel | 1,000 m | 8719605022523 |
History
Update and Revision: | Revision Number: 0.236 Revision Date: 02-20-2024 |