Fieldbus, 1 Pr #18 Str TC, PP ins, OS, PVC Jkt, AIA Armor, PVC Jkt, ISA/SP-50 Type A, PLTC, CM (Category 6A Cable) – Belden (123076F)


Fieldbus, 1 Pair 18AWG (7×26) Tinned Copper, PP insulation, Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, ISA/SP-50 Type A, , PLTC, CM
Our Category 6A Copper Cable offers a wide range of options for your CAT 6A network. Some options that are available include small diameter, snake, industrial, non-bonded, and patented Bonded-Pair. The 10GXS Cable is the industry’s gold standard for performance, while, Belden’s newest cable, 10GXW, is the industry’s smallest-diameter Category 6A cable designed for smart building and multi-gigabit applications with performance optimized for in-building wireless networks.

Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Features & Benefits

  • Reliable network performance: Designed for mission-critical situations that require constant uptime, whether indoor or outside
  • Best-in-class system noise immunity: Achieved through outstanding cable balance, is less susceptible to RFI/EMI in noisy environments
  • Reduce installation time and costs: 10GXW is the smallest and lightest horizontal Category 6A cable available
  • Unparalleled performance: Full 100m channel length under 100W PoE load without derating up to 60°C using 10GXS cables
  • Designed to Last: Higher pulling tensions and tighter bend radii offered by Bonded-Pair Cables

Specifications

Product Overview

Suitable Applications

exposure to rodent, crush, or cut through force, harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor

Element No. of Elements Size Stranding Material
Pair(s) 1 18 AWG 7×26 TC – Tinned Copper

Insulation

Element Material Nom. Thickness Color Code
Pair(s) PP – Polypropylene 0.022 in (0.56 mm) Blue & Orange

Outer Shield

Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7×28) TC

Inner Jacket

Material Nom. Diameter
PVC – Polyvinyl Chloride 0.280 in (7.11 mm)

Armor

Armor Type & Material
AIA – Aluminum Interlock Armor

Outer Jacket

Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.045 in (1.1 mm) 0.585 in (14.9 mm)

Overall Cable Diameter (Nominal)

0.585 in (14.9 mm)

Electrical Characteristics

Electricals

Element Nom. Conductor DCR Nom. Capacitance Cond-to-Shield Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 5.86 Ohm/1000ft (19.2 Ohm/km) 45 pF/ft 100 Ohm 66% 5.2 Amps per Conductor

Nom. Outer Shield DCR

7.5 Ohm/1000ft (25 Ohm/km)

High Frequency (Nominal/Typical)

Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 0.039 0.08 dB/100ft

High Frequency

Frequency [MHz] Max. Insertion Loss (Attenuation)
0.031 0.091 dB/100ft

Voltage

UL Voltage Rating
300 V (CM, PLTC)

Mechanical Characteristics

Temperature

UL Temperature Operating
105°C -40°C to +105°C

Bend Radius

Stationary Min. Installation Min.
6 in (150 mm) 6 in

Resources

Max. Pull Tension

60 lbs (27 kg)

Bulk Cable Weight

38 lbs/1000ft (57 kg/km)

DataTuff Fiber Optic Renewable Grade Cable
Copper Catalog
Blade Slot Selection Table

SKU: BELDEN-123076F Categories: , , ,

Brand

Belden

You were not leaving your cart just like that, right?

Enter your details below to save your shopping cart for later. And, who knows, maybe we will even send you a sweet discount code :)