Specifications
Product Classification
Regional Availability | Asia | Australia/New Zealand | EMEA | Latin America | North America |
Portfolio | CommScope® |
Product Type | Fiber indoor/outdoor cable |
Product Series | Z-DS |
General Specifications
Cable Type | Distribution |
Construction Type | Non-armored |
Jacket Color | Black |
Jacket Marking | Feet |
Total Fiber Count | 24 |
Dimensions
Diameter Over Jacket | 8.7 mm | 0.343 in |
Representative Image
Click on image to enlarge. |
|
Mechanical Specifications
Minimum Bend Radius, loaded | 130 mm | 5.118 in |
Minimum Bend Radius, unloaded | 87 mm | 3.425 in |
Tensile Load, long term, maximum | 400 N | 89.924 lbf |
Tensile Load, short term, maximum | 1335 N | 300.12 lbf |
Compression | 22 N/mm | 125.623 lb/in |
Compression Test Method | FOTP-41 | IEC 60794-1 E3 |
Flex | 100 cycles |
Flex Test Method | FOTP-104 | IEC 60794-1 E6 |
Impact | 5.88 N-m | 52.042 in lb |
Impact Test Method | FOTP-25 | IEC 60794-1 E4 |
Strain | See long and short term tensile loads |
Strain Test Method | FOTP-33 | IEC 60794-1 E1 |
Twist | 10 cycles |
Twist Test Method | FOTP-85 | IEC 60794-1 E7 |
Vertical Rise, maximum | 500 m | 1640.42 ft |
Optical Specifications
Fiber Type | OM4, LazrSPEED® 550 | OM4, LazrSPEED® 550 |
Environmental Specifications
Installation temperature | -30 °C to +60 °C (-22 °F to +140 °F) |
Operating Temperature |
-40 °C to +70 °C (-40 °F to +158 °F) |
Storage Temperature | -40 °C to +75 °C (-40 °F to +167 °F) |
Cable Qualification Standards | ANSI/ICEA S-104-696 | EN 187105 | Telcordia GR-20 (water penetration) | Telcordia GR-409 |
EN50575 CPR Cable EuroClass Fire Performance | Dca |
EN50575 CPR Cable EuroClass Smoke Rating | s1a |
EN50575 CPR Cable EuroClass Droplets Rating | d1 |
EN50575 CPR Cable EuroClass Acidity Rating | a2 |
Environmental Space | Low Smoke Zero Halogen (LSZH) | Riser |
Flame Test Listing | NEC OFNR-ST1 (ETL) and c(ETL) |
Flame Test Method | IEC 60332-3 | IEC 60754-2 | IEC 61034-2 | UL 1666 | UL 1685 |
Documentation & Downloads Building Information Modeling (BIM) Objects Revit BIM Models Declaration of Performance EN50575 DoP EuroClass Dca s1a d1 a2 (Danish) EN50575 DoP EuroClass Dca s1a d1 a2 (Dutch) EN50575 DoP EuroClass Dca s1a d1 a2 (English) EN50575 DoP EuroClass Dca s1a d1 a2 (French) EN50575 DoP EuroClass Dca s1a d1 a2 (German) EN50575 DoP EuroClass Dca s1a d1 a2 (Italian) EN50575 DoP EuroClass Dca s1a d1 a2 (Spanish) Installation Instruction CommScope Fiber Optic Single-Unit Distribution Cable Installation Instructions Product Compliance Documentation Global Trade Data Statement of Compliance RoHS/REACH Product Specification 760070300 Product specifications 760070300 Product specifications (Comprehensive) Warranty CommScope Limited Product Warranty
Building Information Modeling (BIM) Objects Revit BIM Models Declaration of Performance EN50575 DoP EuroClass Dca s1a d1 a2 (Danish) EN50575 DoP EuroClass Dca s1a d1 a2 (Dutch) EN50575 DoP EuroClass Dca s1a d1 a2 (English) EN50575 DoP EuroClass Dca s1a d1 a2 (French) EN50575 DoP EuroClass Dca s1a d1 a2 (German) EN50575 DoP EuroClass Dca s1a d1 a2 (Italian) EN50575 DoP EuroClass Dca s1a d1 a2 (Spanish) Installation Instruction CommScope Fiber Optic Single-Unit Distribution Cable Installation Instructions Product Compliance Documentation Global Trade Data Statement of Compliance RoHS/REACH Product Specification 760070300 Product specifications 760070300 Product specifications (Comprehensive) Warranty CommScope Limited Product Warranty BrandCommScopeYou were not leaving your cart just like that, right?Enter your details below to save your shopping cart for later. And, who knows, maybe we will even send you a sweet discount code :) |