NH50106UFA – DataTuff™ Industrial Ethernet CAT6 4X2X23AWG/1 U/FTP SWA Fire Resistant (PH120)


Call for Price

This product requires special shipping arrangements. Please Use the "ADD TO QUOTE BUTTON" or call us at (866) 650-3282 for more information.

Compare

Product Overview

Suitable Applications: Industrial Ethernet Cat 6 connection with Fire Resistant capability

Construction Details

Conductor
Element Size Stranding Material No. of Pairs No. of Elements
Conductor(s) 23 Solid BC – Bare Copper 4 8
Insulation
Material Nom. Insulation Diameter Color Code Notes
PE – Polyethylene 1.58 mm (0.0622 in) Blue & White with Blue Strip, Orange & White with Orange Strip, Green & White with Green Strip, Brown & White with Brown Strip Fire Protection Barrier: Mica glass Tape(MGT), Twist Direction = S, 25% AL-mylar tape(Overlapping)
Inner Shield
Drainwire Type Notes
26 AWG (Solid) TC Fire Protection Barrier: Mica Glass Tape(MGT)
Inner Jacket
Material Nom. Diameter
LSZH – Low Smoke Zero Halogen (Flame Retardant) 11.80 mm (0.4646 in)
Armor
Armor Type & Material
SWA – Steel Wire Armor
Outer Jacket
Material Nom. Diameter
LSZH – Low Smoke Zero Halogen (Flame Retardant) 15.30 mm (0.6024 in)

Electrical Characteristics

Electricals
Max. Conductor DCR Max. Capacitance Unbalance Nom. Characteristic Impedance
73.2 Ohm/km (22.3 Ohm/1000ft) 330 pF/100m 100 Ohm
Delay
Max. Delay Max. Delay Skew
536 ns/100m 45 ns/100m
High Frequency
Frequency [MHz] Max. Insertion Loss (Attenuation) [dB/100m] Min. NEXT [dB] Min. PSNEXT [dB] Min. ACRF (ELFEXT) [dB] Min. PSACRF (PSELFEXT) [dB] Min. RL (Return Loss) [dB]
1 2.03 74.3 72.3 67.8 64.8 20
4 3.78 65.3 63.3 55.8 52.8 23
8 5.32 60.8 58.8 49.7 46.7 24.5
10 5.95 59.3 57.3 47.8 44.8 25
16 7.55 56.2 54.2 43.7 40.7 25
20 8.47 54.8 52.8 41.8 38.8 25
25 9.51 53.3 51.3 39.8 36.8 24.3
31.25 10.67 51.9 49.9 37.9 34.9 23.6
62.5 15.38 47.4 45.4 31.9 28.9 21.5
100 19.8 44.3 42.3 27.8 24.8 20.1
200 28.98 39.8 37.8 21.8 18.8 18
250 32.85 38.3 36.3 19.8 16.8 17.32
Voltage
UL Voltage Rating
60 V

Mechanical Characteristics

Temperature
Operating
-40°C To +80°C

Standards and Compliance

Environmental Suitability: UV Resistance, Oil Resistance
Flammability / Reaction to Fire: IEC 60332-1-2, IEC 60332-3-22, IEC 60331-23, BS EN 50200 PH120
TIA/EIA Compliance: EIA/TIA 568
ISO/IEC Compliance: IEC 61034-2 – Smoke Density Min Transmittance = 60%
European Halogen Free Standards: IEC 60754-1 – Halogen Amount = 0.50%, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 10 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3
Other Standard Compliance(s): BS EN 50289-4-16

History

Update and Revision: Revision Number: 0.32 Revision Date: 12-12-2023