Product Overview
Suitable Applications: | For Control Applications up to 300V |
Construction Details
Element | No. of Elements | Size | Material | Notes |
---|---|---|---|---|
Conductor(s) | 4 | 0.5 mm² | BC – Bare Copper | Mica tape wrapped over the conductors |
Material | Color Code |
---|---|
XLPE | Black 1, White 1, Black 2, White 2 |
Shield Type | Material | Coverage | Notes |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | ATC drain wire placed along with Overall Foil shield |
Table Notes: | All pairs laid up together & binded by Non-woven tape binder |
Material |
---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) |
Overall Cable Diameter (Nominal): | 12.0 mm (0.472 in) |
Electrical Characteristics
Max. Conductor DCR |
---|
36.72 ?/km @ 20°C |
Voltage Rating |
---|
300 V |
Mechanical Characteristics
Operating |
---|
-30°C To +90°C |
Bulk Cable Weight: | 130 kg/km (87 lbs/1000ft) |
Standards and Compliance
Flammability / Reaction to Fire: | IEC 60332-1-2, IEC 60331-21, BS 6387 CWZ , SS 299-1 |
GB Compliance: | GB 31247 B1 (d0, t1, a1) |
ISO/IEC Compliance: | Smoke Density as per IEC 61034-2 |
European Halogen Free Standards: | IEC 60754-1 – Halogen Amount = 0.5%, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 4.3 , IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 10 |
Product Notes
Notes: | EN 50228-7, IEC 60332-3C |
History
Update and Revision: | Revision Number: 0.10 Revision Date: 11-08-2023 |