Ideal Product Categories

About Us

cable, vdsl, patch

 

Hyperline- Ideal Industries Cutters - Coax/Twisted Pair Cutters - Twisted Pair Cutters - Coax Cutters - Fiber Cutters Fiber Optic Test Equipment- Ideal Industries


American Tech Supply is now an authorized Hyperline distributor

From copper to fiber, the Hyperline system of products includes everything you need for installation, termination, testing and troubleshooting. And our level of technical expertise, training and customer support ensures that your total cost of ownership is kept to a minimum.

Twisted Pair Cable (U/FTP), 4 pairs, Category 6, Solid, LSZH


 
1 - Outer Jacket
2 - Shield-foil
3 - Drain wire
4 - Solid twisted pair
Specifications:
Meets ANSI/TIA/EIA-568, IEC 61156, ISO/IEC 11801 requirements
Fire safety standard IEC 60332-1, UL 1581 VW-1

Applications:
Cable is used for indoor applications. Fixed installations, high bandwidth digital applications with low BER and high data rates. Data-Centers/System area networks.

Description:
Shielded copper cable with improved performance characteristics, 4 pairs, category 6, solid. Four individually shielded twisted pairs (U/FTP, aluminium face outwards), cabled together with a drain wire and jacketed with a FR-LSZH compound.

Materials:
Conductive material: wire made of annealed electrolytic copper, solid
Conductor insulation: polyolefin, skin-foam-skin layer
Shield: every pair is separately shielded with polyester aluminum foil, which covers 100% of twisted pair
Drain wire: tinned copper
The cable jacket: FR-LSZH (flame retardant low smoke zero halogen compound), grey color

Technical characteristics:
Number of pairs: 4 pairs
Conductor diameter (core): 0.57 mm (0.022") (23 AWG) 
Insulated conductor diameter: 1.31 mm (0.052")
Outer cable diameter: 7.3 mm (0.287")
Tensile strength: ≤ 15.3 kg (150 N)
Minimum bend radius: 70 mm (2.76")
Drain wire diameter: 0.41 mm (0.017") (26 AWG)
Operating temperature: -40°C - +70°C (-104°F - +158°F)
Cable weight per 1000 ft (304.8 m): 15.2 kg (33.5 lbs)
Standard package: 500 m (1640 ft)

Electrical characteristics:
Frequency, MHz Attenuation,
dB/100m (at 20°C)
PSNEXT, dB NEXT, dB RL, dB PS ELFEXT, dB ELFEXT, dB
Typical Cat. 6 Typical Cat. 6 Typical Cat. 6 Typical Cat. 6 Typical Cat. 6 Typical Cat. 6
1 2,0 2,8 90,0 72,3 93,0 75,3 22,0 20,0 90,0 65,0 93,0 68,0
4 3,7 3,8 85,0 63,3 88,0 66,3 25,0 23,0 90,0 53,0 93,0 56,0
10 5,7 6,0 85,0 57,3 88,0 60,4 28,0 25,0 80,0 45,0 83,0 48,0
20 8,1 8,5 85,0 52,8 88,0 55,8 28,0 25,0 80,0 39,0 83,0 42,0
30 10,0 10,5 85,0 50,1 88,0 53,1 27,0 23,8 70,0 35,5 73,0 38,5
100 19,0 19,9 80,0 42,3 83,0 45,3 24,0 21,1 63,0 25,0 66,0 28,0
150 23,6 24,9 80,0 39,7 83,0 42,7 22,0 18,8 60,0 21,5 63,0 24,5
200 27,7 29,1 80,0 37,8 83,0 40,8 21,0 18,0 58,0 19,0 61,0 22,0
250 31,4 33,0 77,0 36,3 80,0 39,3 20,0 17,3 55, 17,0 58,0 20,0


Frequency 1 - 250 MHz
Characteristic Impedance 100 Ohm
Max. DC Resistance (at 20°Ñ) 73 Ohm/km nom.
Resistance unbalance ≤ 2 %
Capacitance Unbalance ≥ 1.2 pF/m
Velocity of Propagation 78 %
Dielectric Strength 700 V/minute
Insulation Resistance ≥ 5 GOhm•km

Ordering:
STP4-C6-SOLID-INDOOR-LSZH Shielded Twisted Pair Cable (U/FTP), Category 6, 4 pairs, Solid, 23 AWG, Indoor, LSZH

Call (866) 342-3721 Or Click On The Chat Button At The Top Of The Page To Talk To One Of Our Representatives

 

 

 

 

 

 

 

BIF-Bend Insensitive Fiber