Ideal Product Categories

About Us

cable, vdsl, patch

 

Hyperline- Ideal Industries Cutters - Coax/Twisted Pair Cutters - Twisted Pair Cutters - Coax Cutters - Fiber Cutters Fiber Optic Test Equipment- Ideal Industries


American Tech Supply is now an authorized Hyperline distributor

From copper to fiber, the Hyperline system of products includes everything you need for installation, termination, testing and troubleshooting. And our level of technical expertise, training and customer support ensures that your total cost of ownership is kept to a minimum.

Unshielded Twisted Pair Cable (UTP), 10/25/50/100 pairs, Solid, Outdoor (Category 3)

Twisted Pair cable UTP, category 3, 10/25/50/100 pairs, solid, outdoor
Specifications:
Meets EIA/TIA 568-B for category 3 requirements
Fire protection – CMX
The cable meets IEC 60332-1 fire safety standard

Description:
Unshielded Copper cable, 10/25/50/100 pairs, category 3, solid
Cable is used for outdoor installation

Materials:
Conductive material: wire made of soft annealed electrolytic copper
Conductor insulation: HDPE
The cable jacket: UV resistant black PE

Electrical characteristics:
Max DC Resistance at 20°C 9.38 Ohm/100 m (2.9 Ohm/100 ft)
Max Resistance Unbalance 5%
Max Capacitance unbalance pair-to-ground at 1kHz 330 pF/100m (100.58 pF/ 100ft)
Characteristic Impedance at 1-16 MHz 85-115 Ohm
Min worst pair Structural Return Loss (SRL) 
at 10 MHz
at 16 MHz

12 dB
10 dB
Max attenuation at 20°C
at 772 kHz
at 1 MHz
at 4 MHz
at 8 MHz
at 10 MHz
at 16 MHz

2.2 dB/100 m (0.67 dB/100 ft) 
2.6 dB/100 m (0.79 dB/100 ft) 
5.6 dB/100 m (1.70 dB/100 ft) 
8.5 dB/100 m (2.59 dB/100 ft) 
9.7 dB/100 m (2.96 dB/100 ft) 
13.1 dB/100 m (3.99 dB/100 ft)
Min worst pair to pair NEXT loss 
at 772 kHz
at 1 MHz
at 4 MHz
at 8 MHz
at 10 MHz
at 16 MHz

43 dB
41 dB
32 dB
27 dB
26 dB
23 dB
Min Relative Velocity of Propagation at 10 MHz 0,585


10 pairs

Twisted Pair cable UTP, category 3, 10 pairs, solid, outdoor 
1 – Jacket
2 – Rip-cord 
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair

Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 8.5 mm (0.33")
Jacket thickness: 1.3 mm (0.051")
Maximum strand pitch: 100 mm (3.93")
Minimum bend radius: 8 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Installation temperature: -10°C – +50°C (+14°F – +122°F)
Operating temperature: -40°C – +50°C (-40°F – +122°F)
Weight per 1000 ft (304.8 m): 17.7 kg (39 lbs)
Standard package: 1000 m (3280 ft)


25 pairs

Twisted Pair cable UTP, category 3, 25 pairs, solid, outdoor 
1 – Jacket
2 – Rip-cord 
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair

Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 12 mm (0.47")
Jacket thickness: 1.3 mm (0.051")
Maximum strand pitch: 100 mm (3.93")
Minimum bend radius: 8 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Installation temperature: -10°C – +50°C (+14°F – +122°F)
Operating temperature: -40°C – +50°C (-40°F – +122°F)
Weight per 1000 ft (304.8 m): 42.7 kg (94.14 lbs)
Standard package: 1000 m (3280 ft)


50 pairs


1 – Jacket
2 – Rip-cord 
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair

Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 16 mm (0.62")
Jacket thickness: 1.5 mm (0.059")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 10 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Installation temperature: -10°C – +50°C (+14°F – +122°F)
Operating temperature: -40°C – +50°C (-40°F – +122°F)
Weight per 1000 ft (304.8 m): 83.2 kg (183.4 lbs)
Standard package: 500 m (1640 ft)


100 pairs

Twisted Pair cable UTP, category 3, 100 pairs, solid, outdoor 
1 – Jacket
2 – Rip-cord 
3 – Protective skin
4 – Polymer tape
5 – Solid twisted pair

Technical characteristics:
Conductor diameter: 0.5 mm (0.019") (24 AWG)
Insulated conductor diameter: 0.9 mm (0.035")
Outer cable diameter: 21 mm (0.82")
Jacket thickness: 1.5 mm (0.059")
Maximum strand pitch: 150 mm (5.9")
Minimum bend radius: 10 outer cable diameters
Conductor elongation: 14% minimum
Rip cord has a breaking strength of 10 kg (98 N)
Installation temperature: -10°C – +50°C (+14°F – +122°F)
Operating temperature: -40°C – +50°C (-40°F – +122°F)
Weight per 1000 ft (304.8 m): 150.9 kg (332.6 lbs)
Standard package: 500 m (1640 ft)

Ordering:
UTPXX-C3-SOLID-OUTDOOR Unshielded Twisted Pair cable (UTP), 10/25/50/100 pairs, solid, outdoor, category 3

XX – pair quantity: 10, 25, 50, 100 pairs 

Call (866) 342-3721 Or Click On The Chat Button At The Top Of The Page To Talk To One Of Our Representatives

 

 

 

 

 

 

 

BIF-Bend Insensitive Fiber